Cooling capacity (kW) |
2.6(0.9÷3.4) |
3.5(1.1÷4.2) |
5.3(1.8÷6.1) |
7.0(2.1÷7.9) |
Heating capacity (min.-max.) (kW) |
2.9(0.8÷3.4) |
3.8(1.1÷4.2) |
5.6(1.4÷6.7) |
7.3(1.6÷8.8) |
Energy efficiency class cooling/heating |
A++/A+ |
A++/A+ |
A++/A+ |
A++/A+ |
SEER |
6.2 |
6.1 |
7.1 |
6.1 |
SCOP |
4 |
4 |
4 |
4 |
Power consumption cooling (W) |
710(100÷1240) |
1237(130÷1580) |
1539(140÷2360) |
2345(160÷2960) |
Power consumption heating (W) |
739(120÷1200) |
964(100÷1580) |
1480(200÷2410) |
2035(260÷3140) |
Operating current cooling (A) |
3.1(0.4÷5.4) |
5.4(0.5÷6.9) |
6.9(0.6÷10.3) |
10.2(0.7÷13.3) |
Operating current heating (A) |
3.2(0.5÷5.2) |
4.2(0.4÷6.9) |
6.4(0.9÷10.5) |
10.2(1.1÷13.3) |
Air flow of indoor unit (m3/h) |
520/460/360 |
600/500/360 |
840/680/540 |
980/817/662 |
Air flow of outdoor unit (m3/h) |
1700 |
1700 |
2500 |
3000 |
Operating temp. indor cooling/heating (°C) |
17÷32/0÷30 |
17÷32/0÷30 |
17÷32/0÷30 |
17÷32/0÷30 |
Operating temp. outdor cooling/heating (°C) |
-15÷50/-25÷30 |
-15÷50/-25÷30 |
-15÷50/-25÷30 |
-15÷50/-25÷30 |
Sound pressure of indoor unit (dB) |
40/30/26/21 |
40/34/26/22 |
44/37/30/25 |
44.5/42/34.5/28 |
Sound pressure of outdoor unit (dB) |
55.5 |
56 |
56 |
59.5 |
Dimensions of indoor unit w/h/d (mm) |
805/285/194 |
805/285/194 |
957/302/213 |
1040/327/220 |
Dimensions of outdoor unit w/h/d (mm) |
700/550/275 |
700/550/275 |
800/554/333 |
845/702/363 |
Packing of indoor unit w/h/d (mm) |
870/360/270 |
870/360/270 |
1035/380/295 |
1120/310/405 |
Packing ofoutdoor unit w/h/d (mm) |
815/615/325 |
815/615/325 |
920/615/390 |
965/765/395 |
Net weight ofi ndoor unit (kg) |
7.5 |
7.5 |
10 |
10 |
Net weight of outdoor unit (kg) |
22.7 |
22.7 |
34 |
51.5 |
Gross weight of indoor unit (kg) |
9.7 |
9.7 |
13 |
15.8 |
Gross weight of outdoor unit (kg) |
25.2 |
25.2 |
36.7 |
54.5 |
Pipe diameters liquid/gas (mm) |
6.35/9.52 |
6.35/9.52 |
6.35/12.7 |
9.52/15.9 |
Max. lenght of installation (m) |
25 |
25 |
30 |
50 |
Max. difference ininstallation (m) |
10 |
10 |
20 |
25 |
Power supply outdoor unit (V/Hz/Ph) |
220÷240/50/1 |
220÷240/50/1 |
220÷240/50/1 |
220÷240/50/1 |
Protection outdoor unit (A) |
10 |
16 |
16 |
20 |
Power supply wires outdoor unit |
3x1.5 |
3x1.5 |
3x2.5 |
3x2.5 |
Control wires indoor-outdoor unit |
5x1.5 |
5x1.5 |
5x1.5 |
5x1.5 |
Factory amount of refrigerant up to 5 rm (kg) |
0.5 |
0.5 |
1 |
1.6 |
Extra amount of refrigerant above 5 rm (g/m) |
12 |
12 |
12 |
24 |